Enclosure
size
Drive type
Fuse Class
Fast Acting
(T/J) [A]
Mains, Motor, and brake re-
sistor cable Cu [AWG]
(1)(2)
Mains terminal [AWG]
Grounding terminal
[AWG]
0031 5
FR6
0038 5
50
3*8 AWG + 8 AWG
14 AWG - 1 AWG Cu
10 AWG - 1 AWG Al
14 AWG - 2 AWG
0048 2
0045 5
60
3*8 AWG + 8 AWG
14 AWG - 1 AWG Cu
10 AWG - 1 AWG Al
14 AWG - 2 AWG
0061 2
0061 5
90
3*6 AWG + 6 AWG
14 AWG - 1 AWG Cu
10 AWG - 1 AWG Al
14 AWG - 2 AWG
FR7
0075 2
0072 5
90
3*4 AWG + 6 AWG
14 AWG - 1 AWG Cu
10 AWG - 1 AWG Al
10 AWG - 2/0 AWG
0088 2
0087 5
110
3*2 AWG + 6 AWG
14 AWG - 1 AWG Cu
10 AWG - 1 AWG Al
10 AWG - 2/0 AWG
0114 2
0105 5
150
3*2 AWG + 4 AWG
14 AWG - 1 AWG Cu
10 AWG - 1 AWG Al
10 AWG - 2/0 AWG
FR8
0140 2
0140 5
175
3*2/0 AWG + 2 AWG
4 AWG - 3/0 AWG Cu/Al
10 AWG - 3/0 AWG
0170 2
0168 5
250
3*3/0 AWG + 1/0 AWG
3/0 AWG - 350 kcmil Cu/Al 10 AWG - 3/0 AWG
0205 2
0205 5
250
3*300 kcmil + 2/0 AWG
3/0 AWG - 350 kcmil Cu/Al 10 AWG - 3/0 AWG
FR9
0261 2
0261 5
350
3*350 kcmil + 3/0 AWG
2*(3*250 kcmil + 2/0 AWG)
3/0 AWG - 350 kcmil Cu/Al 10 AWG - 3/0 AWG
0300 2
0300 5
400
2*(3*250 kcmil + 2/0 AWG)
3/0 AWG - 350 kcmil Cu/Al 10 AWG - 3/0 AWG
1
Uses a correction factor 0.7
2
Use cables with a +90 °C (194 °F) heat resistance to comply with the UL standards.
12.3.4 Cable and Fuse Sizes for 525–690 V, FR6 to FR9
Table 41: Cable and Fuse Sizes for VACON
®
NXS/NXP
Enclosure
size
Drive type
I
L
[A]
Fuse
(gG/gL) [A]
Mains, motor, and
brake resistor cable
Cu
(1)
[mm
2
]
Mains terminal [mm
2
] Grounding terminal
[mm
2
]
FR6
0004 6–0007 6 3–7
10
3*2.5+2.5
2.5–50 Cu
6–50 Al
2.5–35
0010 6–0013 6 10–13
16
3*2.5+2.5
2.5–50 Cu
6–50 Al
2.5–35
AQ275638903263en-000601 / DPD00910
148 | Danfoss A/S © 2022.12
Specifications
VACON® NXS/NXP Air-cooled
Operating Guide