4.
-
-
5.
6.
-
-
-
Connect the cables. See the correct tightening torques in
12.6 Tightening Torques of the Terminals
Connect the phase conductors of the mains cable and of the motor cable into the correct terminals. If a brake resistor
cable is used, connect its conductors into the correct terminals.
Attach the grounding conductor of each cable to a grounding terminal with a grounding clamp for grounding con-
ductor.
To make a 360° connection with the grounding clamp for cable shield, expose the shield of motor cables.
e3
0b
g1
04
.2
0
2
1
1
Grounding clamp
2
Exposed shield
Attach the cable entry plate, and then the cable cover. For the tightening torques of the screws, see
. Make sure that the control cables or the cables of the AC drive are not caught between the frame
and the cable cover.
Additional tightening torques:
motor cable entry plate: 2.4 Nm
control cable entry plate: 0.8 Nm
DC cover: 2.4 Nm
AQ275638903263en-000601 / DPD00910
68 | Danfoss A/S © 2022.12
Electrical Installation
VACON® NXS/NXP Air-cooled
Operating Guide