6.
-
-
7.
-
8.
Connect the cables. See the correct tightening torques in
12.6 Tightening Torques of the Terminals
.
Connect the phase conductors of the mains cable and of the motor cable, and the conductors of the brake resistor
cable into the correct terminals.
Attach the grounding conductor of each cable with a grounding clamp.
Make sure to connect the grounding conductor to the motor and the terminals that are identified with the grounding sym-
bol.
If a double grounding is necessary, use the grounding terminal below the drive. Use an M5 screw and tighten it to 2.0
Nm or 17.7 lb-in.
e
3
0
b
g
0
9
3
.1
0
12.5 Tightening Torques for Cover Screws
.
AQ275638903263en-000601 / DPD00910 | 65
Danfoss A/S © 2022.12
Electrical Installation
VACON® NXS/NXP Air-cooled