Enclosure
size
Drive type
I
L
[A]
Fuse
(gG/gL) [A]
Mains, motor, and
brake resistor cable
Cu
(1)
[mm
2
]
Mains terminal [mm
2
] Grounding terminal
[mm
2
]
0018 6
18
20
3*4+4
2.5–50 Cu
6–50 Al
2.5–35
0022 6
22
25
3*6+6
2.5–50 Cu
6–50 Al
2.5–35
0027 6–0034 6 27–34
35
3*10+10
2.5–50 Cu
6–50 Al
2.5–35
FR7
0041 6
41
50
3*10+10
2.5–50 Cu
6–50 Al
6–50
0052 6
52
63
3*16+16
2.5–50 Cu
6–50 Al
6–50
FR8
0062 6–0080 6 62–80
80
3*25+16
25–95 Cu/Al
6–95
0100 6
100
100
3*35+16
FR9
0125 6–0144 6
0170 6
125–144
170
160
200
3*95+50
95–185 Cu/Al
6–95
0208 6
208
250
3*150+70
1
Uses a correction factor 0.7
12.3.5 Cable and Fuse Sizes for 525–690 V (UL Rating 600 V), FR6 to FR9, North America
Table 42: Cable and Fuse Sizes for VACON
®
NXS/NXP, North America, UL Rating 525–600 V
Enclosure
size
Drive type
Fuse Class
Fast Acting
(T/J) [A]
Mains, Motor, and brake
resistor cable Cu [AWG]
(1)(2)
Mains terminal [AWG]
Grounding terminal
[AWG]
FR6
0004 6–0007 6 10
3*14 AWG + 14 AWG
14 AWG - 1 AWG Cu
10 AWG - 1 AWG Al
14 AWG - 2 AWG
0010 6
15
3*14 AWG + 14 AWG
14 AWG - 1 AWG Cu
10 AWG - 1 AWG Al
14 AWG - 2 AWG
0013 6
20
3*14 AWG + 14 AWG
14 AWG - 1 AWG Cu
10 AWG - 1 AWG Al
14 AWG - 2 AWG
0018 6
25
3*12 AWG + 12 AWG
14 AWG - 1 AWG Cu
10 AWG - 1 AWG Al
14 AWG - 2 AWG
0022 6
30
3*10 AWG + 10 AWG
14 AWG - 1 AWG Cu
10 AWG - 1 AWG Al
14 AWG - 2 AWG
0027 6
40
3*8 AWG + 8 AWG
14 AWG - 1 AWG Cu
10 AWG - 1 AWG Al
14 AWG - 2 AWG
AQ275638903263en-000601 / DPD00910 | 149
Danfoss A/S © 2022.12
Specifications
VACON® NXS/NXP Air-cooled
Operating Guide