Code
Description
5
The mains voltage:
2 = 208–240 V
5 = 380–500 V
6 = 525–690 V (IEC)
525–600 V (cULus)
A
The control panel:
A = standard (text display)
B = no local control panel
F = dummy keypad
G = graphical display
2
The protection rating:
0 = IP00
2 = IP21 (UL Type 1)
5 = IP54 (UL Type 12)
T = flange-mounted (through-hole mounted), power part IP54, control part IP21
Z = flange-mounted (through-hole mounted), power part IP54, control part IP00
H
The EMC emission level:
C = complies with the category C1 of standard IEC/EN 61800-3 + A1, 1st environment, and nominal voltage
less than 1000 V
H = complies with the category C2 of standard IEC/EN 61800-3 + A1, fixed installations, and nominal voltage
less than 1000 V
L = complies with the category C3 of standard IEC/EN 61800-3 + A1, 2nd environment, and nominal voltage
less than 1000 V
T = complies with the standard IEC/EN 61800-3 + A1 when used in IT networks (C4).
N = No EMC emission protection. An external EMC filter is necessary.
1
The brake chopper:
(1)
0 = No brake chopper
1 = Internal brake chopper
2 = Internal brake chopper and resistor, available for:
208–240 V (FR4–FR6)
380–500 V (FR4–FR6)
SSV
The hardware changes:
The supply, the first letter (
X
xx):
S = 6-pulse connection (FR4 to FR11)
B = Additional DC-connection (FR8 to FR11)
O = Standard and input switch (Standalone)
J = FR10 to 11 standalone with main switch and DC-link terminals
AQ275638903263en-000601 / DPD00910