Enclosure size
Drive type
Tightening torque (Nm)
Tightening torque (in-lb)
0125 6–0208 6
FR10 Standalone
0385 5–0520 5
0261 6–0416 6
40
354
FR11 Standalone
0590 5–0730 5
0460 6–0590 6
40
354
12.7 Power ratings
12.7.1 Overload Capability
The
low overload
means that if 110% of the continuous current (I
L
) is required for 1 minute every 10 minutes, the remaining 9
minutes must be approximately 98% of I
L
or less. This is to make sure that the output current is not more than I
L
during the duty
cycle.
e
3
0
b
g
0
3
8
.1
0
IL
IL*110%
1 min
9 min
I
t
IL*110%
Illustration 74: Low Overload
The
high overload
means that if 150% of the continuous current (I
H
) is required for 1 minute every 10 minutes, the remaining 9
minutes must be approximately 92% of I
H
or less. This is to make sure that the output current is not more than I
H
during the duty
cycle.
e
3
0
b
g
0
3
9
.1
0
IH
IH*150%
1 min
9 min
IH*150%
I
t
Illustration 75: High Overload