Drive type
A
B
C
D
0062 6–0100 6
(1)
0261 2–0300 2
0261 5–0300 5
0125 6–0208 6
50
(1.97)
80
(3.15)
400
(15.75)
250 / 350
(9.84) / (13.78)
(2)
1
To change the fan with the motor cables connected, the necessary clearance on the 2 sides of the drive is 150 mm (5.91 inch).
2
The minimum clearance to change the fan.
Table 7: Required Cooling Air
Drive type
The quantity of cooling air [m
3
/h]
The quantity of cooling air [CFM]
0003 2–0012 2
0003 5–0012 5
70
41.2
0017 2–0031 2
0016 5–0031 5
190
112
0048 2–0061 2
0038 5–0061 5
0004 6–0034 6
425
250
0075 2–0114 2
0072 5–0105 5
0041 6–0052 6
425
250
0140 2–0205 2
0140 5–0205 5
0062 6–0100 6
650
383
0261 2–0300 2
0261 5–0300 5
0125 6–0208 6
1000
589
5.2.3 Cooling of Standalone AC drives (FR10 to FR11)
AQ275638903263en-000601 / DPD00910 | 35
Danfoss A/S © 2022.12
Mounting the Unit
VACON® NXS/NXP Air-cooled
Operating Guide