ED34-862
Specifications
FXMQ-P
247
7
Ceiling Mounted Duct Type
Note:
∗
1
Indoor temp. : 27°CDB, 19.5°CWB / outdoor temp. : 35°CDB / Equivalent piping length : 7.5 m, level difference : 0 m.
∗
2
Indoor temp. : 27°CDB, 19.0°CWB / outdoor temp. : 35°CDB / Equivalent piping length : 7.5 m, level difference : 0 m.
∗
3
External static pressure is changeable in 13 or 14 stages within the ( ) range by remote controller.
∗
4
Air filter is not standard accessory, but please mount it in the duct system of the suction side. Select its colorimetric method (gravity method)
50% or more.
5
Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
∗
6
Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre. During actual operation, these values are
normally somewhat higher as a result of ambient conditions.
7
Refer to page 255 for Fan Motor Input.
Model
FXMQ100PVE
FXMQ125PVE
∗
1 Cooling Capacity (19.5°CWB)
kcal/h
10,000
12,500
Btu/h
39,600
49,500
kW
11.6
14.5
∗
2 Cooling Capacity (19.0°CWB)
kW
11.2
14.0
Casing
Galvanized Steel Plate
Galvanized Steel Plate
Dimensions: (H×W×D)
mm
300×1,400×700
300×1,400×700
Coil (Cross
Fin Coil)
Rows×Stages×Fin Pitch
mm
3×16×1.75
3×16×1.75
Face Area
m²
0.383
0.383
Fan
Model
—
—
Type
Sirocco Fan
Sirocco Fan
Motor Output × Number
of Units
W
350×1
350×1
Air Flow Rate (HH/H/L)
m³/min
32/27/23
39/33/28
cfm
1,130/953/812
1,377/1,165/988
External Static
Pressure
Pa
Standard 100 (200-50
∗
3)
Standard 100 (200-50
∗
3)
Drive
Direct Drive
Direct Drive
Temperature Control
Microprocessor Thermostat for Cooling and Heating
Microprocessor Thermostat for Cooling and Heating
Air Filter
∗
4
∗
4
Piping
Connections
Liquid Pipes
mm
φ
9.5 (Flare Connection)
φ
9.5 (Flare Connection)
Gas Pipes
mm
φ
15.9 (Flare Connection)
φ
15.9 (Flare Connection)
Drain Pipe
mm
VP25
External Dia. 32
Internal Dia. 25
VP25
External Dia. 32
Internal Dia. 25
Mass (Weight)
kg
46
46
∗
6 Sound Level (HH/H/L)
dBA
220V
43/41/39
44/42/40
240V
43/41/39
44/42/40
Safety Devices
Fuse.
Fan Driver Overload Protector.
Fuse.
Fan Driver Overload Protector.
Refrigerant Control
Electronic Expansion Valve
Electronic Expansion Valve
Connectable Outdoor Unit
R-410A PA Series
R-410A PA Series
Standard Accessories
Operation Manual. Installation Manual. Drain Hose. Clamp
Metal. Insulation for Fitting. Sealing Pads. Clamps.
Washers. Screws. Air Discharge Flange. Air Suction
Flange.
Operation Manual. Installation Manual. Drain Hose. Clamp
Metal. Insulation for Fitting. Sealing Pads. Clamps.
Washers. Screws. Air Discharge Flange. Air Suction
Flange.
Drawing No.
C : 3D060388A
(
)
(
)
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3412
cfm=m³/min×35.3