ED34-862
Installation
FXCQ-M
137
3
Drain Pump Kit
Drain Piping Work
〈〈
Rig the drain pipe as shown below and take measures against condensation. Improperly rigged piping
could lead to leaks and eventually wet furniture and belongings.
〉〉
(1) Carry out the drain piping
• The diameter of the drain pipe should be greater than or equal to the diameter of the connecting pipe
(vinyl tube ; pipe size : 25 mm ; outer dimension : 32 mm).
• Keep the drain pipe short and sloping downwards at a gradient of at least 1 / 100 to prevent air pockets from forming.
• If the drain hose cannot be sufficiently set on a slope, execute the drain raising piping.
• To keep the drain hose from sagging, space hanging wires every 1 to 1.5 m.
CAUTION
Setting the unit at an angle opposite to the drain piping might cause leaks.
•
Use the drain hose and the metal clamp.
Insert the drain hose into the drain socket, up to the tape.
Tighten the clamp until the screw head is less than 4 mm from the hose.
•
Wrap the attached sealing pad over the clamp and drain hose to insulate.
•
Insulate the drain hose inside the building.
〈
PRECAUTIONS FOR DRAIN RAISING PIPING
〉
•
Install the drain raising pipes at a height of less than 310 mm.
•
Install the drain raising pipes at a right angle to the indoor unit and no more than 300 mm from the unit.
•
If converging multiple drain pipes, install according to the procedure shown below.
Select converging drain pipes whose gauge is suitable for the operating capacity of the unit.
3PR01906-7R
Indoor unit
Drain pump kit
FXCQ–M
Standard (Equipped with indoor unit)
1-1.5m
1-1.5m
Hanger
bracket
Metal clamp
Drain hose
Tape
≤
4mm
Large sealing
pad
Metal clamp
(accessory)
(accessory)
Ceiling slab
≤
600
mm
( ≤
310mm)
290
mm
1-1.5m
≤
300mm
Hanger bracket
Adjustable
Drain raising pipe
Drain hose (accessory)
Metal clamp
(accessory)
T-joint converging drain pipes
≥
100mm