Installation
ED34-862
326
FXHQ-MA
9. Installation
Installation Example
Service Space
(1) Select an installation site where the following conditions are fulfilled and that meets your customer’s
approval.
• In the upper space of the indoor unit where there is no possible dripping of water from the refrigerant pipe, drain
pipe, water pipe, etc.
• Where optimum air distribution can be ensured.
• Where nothing blocks air passage.
• Where condensate can be properly drained.
• If supporting structural members are not strong enough to take the unit’s weight, the unit could fall out of place
and cause serious injury.
• Where the false ceiling is not noticeably on an incline.
• Where there is no risk of flammable gas leakage.
• Where sufficient clearance for maintenance and service can be ensured.
(Refer to Fig. 1)
If sufficient clearance could be ensured at*, leave a space of 200 mm or more between the unit and it’s surround-
ings easier maintenance and service.
• Where piping between indoor and outdoor units is possible within the allowable limit. (Refer to the installation
manual for the outdoor unit.)
CAUTION
• Install the indoor and outdoor units, power supply wiring and connecting wires at least 1 meter away from tele-
visions or radios in order to prevent image interference or noise.
(Depending on the radio waves, a distance of 1 meter may not be sufficient enough to eliminate the noise.)
(2) This indoor unit may be installed on ceilings up to 3.5 m in height. However, if the ceiling is higher than
2.7m, the remote control will have to be set locally. (Refer to “FIELD SETTING”)
(3) Use suspension bolts for installation. Check whether the ceiling is strong enough to support the weight
of the unit or not. If there is a risk, reinforce the ceiling before installing the unit.
(Installation pitch is marked on the paper pattern for installation. Refer to it to check for points requiring reinforcing.)
C : 3PN01417-7P
Air outlet
Drain pipe
Refrigerant pipe
Grounding wire
Remote controller
Suction grille
Air filter (inside suction grille)
Transmission wiring
Air flow flap (at air outlet)
Conducts electricity from the unit into the
ground to prevent electric shock.
C : 3PN02401-4Y
*
≥
30
*
≥
30
≥
300
2500 or higher
from the floor
For installation
in high places
Air inlet
Air outlet
Obstruction
Floor
Required service
space
(length : mm)
Fig. 1