Installation
ED34-862
444
FXMQ-MF
ELECTRICAL CHARACTERISTICS
SPECIFICATIONS FOR FIELD SUPPLIED FUSES AND WIRE
NOTES
1. Select the particular size of electrical wire for power supply wire in accordance with the standards of the given
nation and region.
2. Allowable length of transmission wire between indoor/out-door units and between the indoor unit and the remote
con-troller is as follows.
(1) Outdoor unit – Indoor unit:
Max. 1000 m (Total wiring length: 2000 m)
(2) Indoor unit – Remote controller:
Max. 500 m
(3) Max. branches No. of branches :16
3. Insulated thickness: 1mm or more
4. Up to 16 branches are possible for unit-to unit cabling. No branch is allowed after first branch.
(Refer to Fig. 15)
Wiring Example And How To Set The Remote Controller
HOW TO CONNECT WIRINGS (Remove the electric parts box lid and wire as shown in the
figure below.)
Units
Power supply
Fan motor
Model
Hz
Volts
Voltage range
MCA
MFA
KW
FLA
FXMQ125MFV1
50
220 - 240
Max. 264
Min. 198
1.9
15
0.380
1.5
FXMQ200MFV1
3.3
15
0.380
2.6
FXMQ250MFV1
3.8
15
0.380
3.0
MCA:
Min. Circuit Amps (A);
MFA:
Max. Fuse Amps (A)
KW:
Fan Motor Rated Output (kW);
FLA:
Full Load Amps (A)
Model
Power supply wiring
Transmission wiring
Field fuses
Wire
Size
Wire
Size
FXMQ125MFV1
15A
H05VV-U3G
Size must comply with
local codes.
Sheathed wire
(2 wire)
0.75 - 1.25 mm²
FXMQ200MFV1
FXMQ250MFV1
F1 F2
F1 F2
F1 F2
F1 F2
F1 F2
Branch
Subbranching
Fig. 15
Remote controller
wire
Transmission
terminal block (X2M)
Power supply
terminal block (X1M)
Power supply
wire
Ground wire
Electric parts box lid
Fig. 16
Transmission
wire