ED34-862
Accessories
FXFQ-P
93
2
J : 1P191031A
Horizontal blade absorbent 17
Rib
A-A cross section
Setting switch number
Mode number
02
1
13 (23)
2-way blow
(Number of air outlets used)
03
Setting position number
3-way blow
Horizontal blade
Backside
Standard
Mode number
[Setting content]
(Setting for when corner air outlet is blocked with 4-way blow)
(Wind direction)
Setting position number
Slightly downward
13 (23)
02
4
03
4.2m or less
3.0m or less
3.8m or less
High ceiling 2
Number of air outlets used
Types 100~
3.9m or less
3.0m or less
3.3m or less
3-way blow
4.2m or less
2.7m or less
3-way blow
4-way blow
3.4m or less
4.2m or less
2-way blow
Types ~80
4.0m or less
All-around blow
All-around blow
4-way blow
3.5m or less
4.2m or less
3.5m or less
Indoor unit
3.1m or less
3.5m or less
High ceiling 1
2-way blow
4.0m or less
3.4m or less
3.6m or less
4.5m or less
3.2m or less
Standard
3.6m or less
Front face
Horizontal blade
16
16
Horizontal blade
Depending on the installation status of the indoor unit's main body, the field setting needs to be performed by remote control operation.
Horizontal blade sealing pad 19
0
01
13 (23)
02
Setting position number
Mode number
[Setting content]
(Setting by ceiling height)
03
Standard
A
B
A
Values for ceiling height are provided as reference.
Using the base of the rib as a reference, stick without leaving any gap.
If the sticking of insulator is omitted, condensation may occur.
B
2
Stick the horizontal blade sealing pad to the backside of the blade. (For both left and right)
19
(Guidelines of ceiling height and number of air outlets used)
Sticking of Insulator to Indoor Unit Main Body
Sticking of Absorbent to Panel Horizontal Blade
Field Setting
For safety, be sure to shut off power supply before starting the insulator sticking operation, decoration panel mounting operation, and connecting of connectors for swinging.
Stick the side insulator plate according to the figure below.
16
Precautions
Side insulator plate
16
Side insulator plate
16
Side insulator plate
16
Side insulator plate
16
Side insulator plate
Sticking reference
16
Sticking reference
16
Sticking reference
16
For a wiring takeoff point with two sections, make a slit on
the side insulator plate as shown in the figure below,
then route the wiring.
Wiring
Wiring
Slit
Slit
16
Side insulator plate
16
Side insulator plate
Wiring takeoff point
Superimpose the surplus section.
Perform the operation on soft cloth to prevent damage to the panel.
Perform sticking for the horizontal blades of all air outlets.
Do not apply force to the horizontal blade. (Application of force may lead to horizontal blade
swing failure.)
1
According to the figure below, stick the horizontal blade absorbent and as well as the horizontal blade
sealing pad .
(With KDBH55K160, stick the horizontal blade absorbent with matching blade colour.)
When the sticking of absorbent and sealant is omitted, condensation may occur.
Stick the horizontal blade absorbent in line with the blade shape to the front face of the horizontal blade.
17
18
19
17
Precautions
Horizontal blade absorbent 17
17
Sticking reference
19
Sticking reference
19
Sticking reference
3
Stick the horizontal blade absorbent in between the horizontal blade sealing pad .
18
19
Horizontal blade absorbent 18
18
Sticking reference
18
Sticking reference
Horizontal blade absorbent 18
Horizontal blade sealing pad 19
B-B cross section
Perform the setting by switching among the following three items: "Mode number", "Setting switch number", and "Setting position number".
The setting procedure and operation method are described in "How to perform field setting" attached to the remote control.
(1) Setting by number of air outlets used
While referring to "How to perform field setting" attached to the remote control, perform the setting according to the table
in the right.
Also, when the corner air outlet is blocked with 4-way blow, set the wind direction slightly downward.
(Note) When the installation height becomes higher than the standard, the setting by ceiling height in (2) becomes
necessary.
(2) Setting by ceiling height
For the ceiling height, refer to the guidelines of ceiling height and number of air outlets used, then perform the setting for
each air outlet used according to the table below.
Ceiling height
[Setting content]
(Setting by number of air outlets used)
High ceiling 2
High ceiling 1