ED34-862
Accessories
FXFQ-P
97
2
KDDP55K160(K) — Fresh Air Intake Kit (Chamber type)
KDDP55K160 (without T-shape, without Fan)
Caution
1. Maximum length of the duct is 4 meters.
2. When installing this kit, an inspection hole is
required (in order to maintain this kit). Establish an
inspection holes on either side.
3. This kit is field assembly.
4. Install the hanging fixing for the T joint. Otherwise
the load from T-shape pipe assembly, etc., could
create a gap between the indoor unit and suction
chamber.
5. When mounting the duct fan, be sure to use the
wiring modification adaptor to interlock with the
indoor unit fan.
6. With the intake wind volume, 10% or less of the “H”
wind volume of the indoor unit is recommended.
7. This graph shows values from the inlet of the T joint
through that of the indoor unit when KDDP55K160K
(with a T joint) is connected.
Dimensions
Unit:mm
Model
KDDP55K160
Item
Fresh air intake method
Fresh air intake by air conditioning fan
Diameter of connection duct
φ
150
Mass (kg)
4.5
Inspection hole
450 or more
(See note 2)
Inspection hole
450 or more
(See note 2)
How to establish an inspection hole
(Ceiling opening dimension)
KDDP55K160K (with T-shape, without Fan)
Caution
1. Maximum length of the duct is 4 meters.
2. When installing this kit, an inspection hole is
required (in order to maintain this kit). Establish an
inspection holes on either side.
3. This kit is field assembly.
4. Install the hanging fixing for the T joint. Otherwise
the load from T-shape pipe assembly, etc., could
create a gap between the indoor unit and suction
chamber.
5. When mounting the duct fan, be sure to use the
wiring modification adaptor to interlock with the
indoor unit fan.
6. With the intake wind volume, 10% or less of the “H”
wind volume of the indoor unit is recommended.
7. This graph shows values from the inlet of the T joint
through that of the indoor unit when KDDP55K160K
(with a T joint) is connected.
Dimensions
Unit:mm
Model
KDDP55K160K
Item
Fresh air intake method
Fresh air intake by air conditioning fan
Diameter of connection duct
φ
150
Mass (kg)
6.5
Inspection hole
450 or more
(See note 2)
Inspection hole
450
or more
(See note 2)
How to establish an inspection hole
(Ceiling opening dimension)
Flexible duct
(Accessory)
T joint
(Accessory)
Suction duct
(Accessory)
Plate band (Accessory)
Hanging fitting (Field supplied)
(See note 4)