Accessories
ED34-862
102
FXFQ-P
J : 2P137676B
3) After mounting the duct flange 1 to the opening using the mounting screws 2 (M4×12, 4 pieces),
stick the duct flange insulator 3 . Figure 3
Figure 3
Duct flange 1
Mounting screws 2
(M4×12, 4 pieces)
Duct flange insulator 3
4) Before mounting the decoration panel, remove the insulator, and stick the sealing pad retainer 5 to
the indoor unit drain pan. Figure 4
Figure 4
Sealing pad retainer 5
Be careful not to
block the air outlet.
Insulator
Duct Connection
<<Duct: Nominal diameter
φ
100>>
1) Connect the duct to the outside of the duct flange. Figure 5
2) After the connection, wrap the connection area with tape (field supplied) to prevent an air leak.
Duct flange 1
Wrap with tape to prevent an air leak.
Indoor unit main body
Precautions
Perform insulation for all ducts.
Do not perform duct manipulations
shown to the right.
Tape
Figure 5
φ
100 duct (field supplied)
a) Extreme bending
b) Multiple bending
c) Reduction of connecting
duct diameter