Precautions
This kit can be mounted to a ceiling mounted cassette-type air conditioner.
When using this kit, a duct (nominal diameter:
φ
100) is required separately.
•
Beware that, in accordance with the local law, there may be cases where the use of a nonflammable duct is compulsory.
• When a duct goes through fire protection areas including a fire proof structure, beware that, in accordance with
the local law
,
it may be required to establish a damper or to build a structure that is not detrimental to fire protection.
• When penetrating a wooden construction wall with a metal duct, apply electrical insulation to the duct and wall.
•
•
Mount the outside duct so that it has a downslope toward the outside, and prevent rainwater from leaking in.
(Gradient of 1/100 to 1/50)
To prevent the intrusion of small animals, such as birds, and bugs, be sure to attach a netting to sections open to
outside air.
Parts content Check the following parts.
Name
Shape
1 Duct flange
5 Sealing pad retainer 6 Installation manual
4 Main body opening insulator
3 Duct flange insulator
2 Mounting screws
Number of pieces
1
1
1
1
1
4
M4×12
Tools needed for mounting
Phillips-type screwdriver, nippers, and cutter, etc.
Mounting of Duct Flange
1) Cut off the side plate of the indoor unit main body along the dowel hole without damaging
the internal insulator.
Side plate
Internal insulator
Cut off using
nippers, etc.
Slit
Piping position
Drain pipe position
Side plate
2) Stick the main body's opening insulator 4 to the opening.
Figure 1
Figure 1
Figure 2
Figure 2
Main body opening insulator 4