Accessories
ED34-862
330
FXHQ-MA
Drain Pump Kit
Specifications
Precaution at use
1. Don't turn off the power within 5 minutes after cooling operation stops.
2. The liquid crystal display blinks to inform us that safety device actuated.
3. When cooling operation's season is over, extract drain water.
Installation guide of the drain pump kit
<Changes in drain pump kit>
Exit drain pipe has been changed from VP25 to VP20 (to meet the drain diameter of main frame).
Attached drain pipe (450 mm chloride vinyl straight pipe bellow, elbow) -> only bellow hose for VP20
All units of drain up height was unified to 600mm (From the bottom of the ceiling)
Wiring diagram
L Shape Connection Pipe Kit
Application purpose
This kit must be bent inside the unit as shown below, when the refrigerant piping is carried out in a ceiling space. This
L shape kit is an optional accessory which has been developed for improving the work of the processing on site.
Installation
Model
Items
KDU50M60VE
KDU50M125VE
Drain-up Lift (mm)
600
Drain Con. Diameter
VP20 (Ex. dia.
φ
26, Int. dia.
φ
20)
Pump
Power Supply
Single phase 220-240V/220V 50Hz
(from Indoor Unit PC Board)
Power
Consumption (W)
20/17 (50Hz)
Applicable Models