Accessories
ED34-862
312
FXMQ-MA
Drain Pump Kit
Specification
Precaution at use
1. When this kit will be used with the natural evaporation pan type humidifier together, the piping of unit's drain and
humidifier's drain can be used in common.
2. Be sure to do test run (cooling) to make sure the drain flows out.
3. Prohibit providing a drain trap when the drain pump kit will be mounted.
Installation Space
Internal Wiring Method
KDU30L250VE
Model
Items
KDU30L250VE
Power Supply
Single phase 220V 50/60Hz
Power Consumption (W)
19/17 (50/60Hz)
Drain-up Lift (mm)
Standard drain outlet of the unit + 222 + 250
Drain Outlet
VP25 (Internal diameter
φ
25, external diameter
φ
32)
Safety Device
Float switch
Weight (kg)
10
Applied Models
200 · 250 Class
KDU30L250VE
Wrong
Good
If the drain pump kit has already been installed, note the following
when installing the indoor unit.
· Do not install the indoor unit on an incline against drainage flow
(away from the drain outlet). This can lead to water leaks.
Fan partition plate
Float switch lead wire
Drain plug
Remove a cushion
Insulator (1)
Drain pump lead wire
Relay harness (1)
Drain pump lead wire
Float
switch
(Drain pump kit)
Indoor PC board
assembly
(Indoor unit)
Remove the short
circuit connector
Float switch
lead wire
X8A