ED34-862
Installation
FXMQ-MA
307
8
Bolt Pitch
(1) Relative positions of indoor unit and suspension bolt.
(Refer to Fig. 2)
(2) Install a canvass duct to the air discharge outlet and air inlet so that vibration from the machine body isn’t
transmitted to the duct or ceiling.
You should also apply acoustic (insulation material) to the inside of the duct, and vibration insulation rubber to the
suspension bolts.
(3) Install suspension bolts. (Use bolts of 10 mm diameter.)
• Install the equipment where supporting structures are strong enough to bear the equipment’s weight. Use
embedded inserts or anchor bolts with new buildings and hole-in-anchors with old buildings.
C : 3P086156-6U
FXMQ200
·
250MAVE
Fig. 2
Indoor unit
Air outlet
Inspection hatch
600
1296
Air inlet
Approx.
150 mm
1100
1100 or more
1148
1380
(service space)
Suspension
bolt (× 4)
(length : mm)
650 or more
(service
space)
Anchor
Indoor unit
Long nut or turn-buckle
Installation example
Note) All the above parts are field supplied.
Suspension bolt
Ceiling slab