ED34-862
Accessories
FXFQ-P
99
2
JC : 3K017588C
Installation of Indoor Unit Main Body and Suction Chamber
Indoor unit
main body
Suction chamber
Flexible duct
Hook
Indoor unit main body
Hook
Ceiling surface
Hook
Suspension bracket
2
6
1
Suspension bracket
3
11
T joint
10
Sealing pad
12
Square hole
Duct (field supplied)
Suction chamber
Precautions
7
Indoor unit main body
Split pin
Suspension bracket
Suspension bracket
Flexible duct
Match the contour
c) Reduction of connecting duct diameter
(
φ
150)
2
Mounting of connecting chamber
(This figure shows the connecting chamber (left) .)
Mounting of Decoration Panel
Mounting of Connecting Chamber and Connection of Flexible Duct
Drawing of mounting
at completion
wrong
BYCP125K-W1
Fixing method of hook
(1)
(2)
(3)
(4)
Connecting chamber (right)
2
Connecting chamber (left)
Drawing of mounting at completion
Status after mounting
Mounting status
b) Multiple bending
Suction chamber
In case of KDDP55K160K
Connecting chamber left (right)
3
( )
<How to Tight Sealing Pad>
Outside air inlet
Screw
(mm)
a) Extreme bending
With wireless unit
180
correct
Figure 4
Figure 5
Figure 6
1
Suction chamber
1
• Install the indoor unit main body and suction chamber.
At the time of installation, perform the engineering work according to the installation
manual attached to the indoor unit main body. (For the installation height, refer to the figure
to the right.)
• When mounting the suction chamber to the existing indoor unit main body, change the
installation height of the indoor unit main body to height in the figure to the right.
• After temporarily hooking the decoration panel, pass the swing motor lead wire, which is coming out from the decoration panel, through the wiring hole of the suction chamber.
However, when used in combination with the air purifier unit or streamer deodorization unit, perform wiring without routing through the wiring hole.
• Mount the decoration panel according to the installation manual attached to the decoration panel.
Figure 7
Figure 8
2
1
6
3
Figure 7
Mount the connecting chamber. (1 piece each for left and right, a total of 2 pieces)
(1) Press the square hole area of the connecting chamber ( ) into the hook
section (tab) of the suction chamber . (2 positions)
(2) Using the supplied screws , fix the connecting chamber. (2 positions)
1
2
3
(Procedure 1)
Press the square hole area of the
connecting chamber ( ) into the
hook section of suction chamber .
(2 positions each)
6
(Procedure 2)
Using the supplied screws , fix the
connecting chamber. (2 positions each)
(1) Wrap the sealing pad
to the position to be
tightened.
(2) Insert the tip of the
band through the
gap of the split pin,
then lightly tighten
by hand.
(3) Using a standard
tool (driver, pliers,
etc.), turn the split
pin to the direction
shown in the figure
to tighten the band.
(4) This completes
the mounting.
Because the split pin has a structure to prevent counter rotation, be careful with the
turning direction. (When a counter rotation is forced, the ratchet will be damaged, and
the tightening force will be weakened.)
(3) Connect the connecting chamber and T joint.
Insert the flexible duct
until the base of the
connecting chamber.
Figure 8
Hanging band for duct
(field supplied)
To prevent applying weight to the
connecting chamber, hang the T
joint using the hanging band for
the duct.
(4) Mount the supplied installation pattern paper to the indoor unit by using screws to
cure the indoor unit.
(Refer to the installation manual of the indoor unit main body.)
(Refer to the figure below.)
(Mounting of installation
pattern paper)
Installation pattern paper
(Supplied with the indoor unit
main body)
Screw
(Supplied with the indoor unit
main body)
• Complete all the refrigerant and drain piping works for the indoor unit main body.
Duct Connection
<<Duct: Nominal diameter
φ
150>>
(1) Connect the duct to the duct connection area.
(2) Wrap the connection area with vinyl tape, etc., (arrangement at site) to prevent an air leak.
Precautions
•
For the duct, be sure to apply the insulation treatment to prevent condensation.
•
Do not perform duct manipulations described in the figure to the right.
•
Beware that, in accordance with the local law, there may be cases where the use of a nonflammable duct is
compulsory.
•
When a duct goes through fire protection areas including a fire proof structure, beware that, in accordance with the local law, it may be required to establish a damper or to build a
structure that is not detrimental to fire protection.
•
When penetrating a wooden construction wall with a metal duct, apply electrical insulation to the duct and wall.
•
Mount the outside duct so that it has a downslope toward the outside, and prevent rainwater from leaking in with a hood, etc. (Gradient of 1/100 to 1/50)
•
To prevent the intrusion of small animals, such as birds, and bugs, be sure to attach a netting to sections open to outside air.
•
To protect the heat exchanger of the indoor unit, be sure to attach an air filter to sections open to outside air.
With an air purifier unit or
streamer deodorization unit
1
1
Suction chamber
Wiring hole
Swing motor lead wire: Route from the panel side to the
suction chamber .
(After temporarily hooking the decoration panel, pass
through the wiring hole.)
Decoration panel
• For details on connection method, refer to the installation manual
attached to the wireless remote control kit (sold separately).