1-20
7
WIRING
WARNING
• Do not use tapped wires, extension cords, or starburst connections, as they may cause overheating, electric shock,
or
fi
re.
• Do not use locally purchased electrical parts inside the product. (Do not branch the power for the drain pump, etc.,
from the terminal block.) Doing so may cause electric shock or
fi
re.
• Be sure to install a earth leakage circuit breaker. (One that can handle higher harmonics.)
(This unit uses an inverter. Therefore, a earth leakage circuit breaker capable of handling higher harmonics must be
used in order to prevent the earth leakage circuit breaker malfunctioning.)
• Use an all-pole disconnection type circuit breaker with at least 3mm (1/8 inch) between the contact point gaps.
• When carrying out wiring, take care not to pull at the conduit.
• Do not connect the power wire to the indoor unit. Doing so may cause electric shock or
fi
re.
• Do not turn on the circuit breaker until all work is completed.
1) Strip the insulation from the wire (20mm).
2) Connect the inter-unit wires between the indoor and outdoor units so that the terminal numbers match. Tighten the
terminal screws securely. It is recommended that a
fl
athead screwdriver be used to tighten the screws.
The screws are packed with the terminal block.
1
2
3
1 2 3
L N
1
2
3
Firmly
fi
x the wires with
the terminal screws.
Power supply wire
3-core 2.5mm
2
or more
60245 IEC 57 H07RN-F
Power supply
50Hz 220-240V
Circuit
breaker
Earth leakage
circuit breaker
RXC20/25/35*
16A
20A
RXC50/60/71*
Inter-unit wire 4-core 1.5mm
2
or
more 60245 IEC 57 H07RN-F
Firmly
fi
x the wires with
the terminal screws.
Earth
Power supply
terminal block
L
N
Shape wires so
that the service
lid and stop valve
cover
fi
t securely.
Forced cooling operation
Using the indoor unit ON/OFF switch
Press the indoor unit ON/OFF switch for at least 5 seconds. (The operation will start.)
• Forced cooling operation will stop automatically after around 15 minutes.
To stop the operation, press the indoor unit ON/OFF switch.
After closing the liquid stop valve, close the gas stop valve within 3 minutes, then stop the forced cooling operation.
CAUTION
To pump down
DANGER: RISK OF EXPLOSION
Pump down - Refrigerant leakage
. If you want to pump down the system, and there is a leakage in the refrigerant circuit:
•
Do NOT use the unit's automatic pump down function, with which you can collect all refrigerant from the system into the
outdoor unit. Possible consequence: Self-combustion and explosion of the compressor because of air going into the
operating compressor.
•
Use a separate recovery system so that the unit's compressor does NOT have to operate.
NOTICE
During pump down operation, stop the compressor before removing the refrigerant piping. If the compressor is still running
and the stop valve is open during pump down, air will be sucked into the system. Compressor breakdown or damage to the
system can result due to abnormal pressure in the refrigerant cycle.
Summary of Contents for FTXC20BV1B
Page 2: ......
Page 30: ...1 28 MEMO...
Page 58: ...2 28 MEMO...
Page 86: ...3 28 MEMO...
Page 114: ...4 28 MEMOR NDUM...
Page 142: ...5 28 M MO...
Page 170: ...6 28 ZET...
Page 172: ...7 2 FTXC20 25 35 50 785 250 288 FTXC60 71 1005 288 297...
Page 174: ...7 4 RXC71 930 695 66 12 610 241 350 23 350 75 98...
Page 175: ...7 5 R32 DAIKIN AIR CONDITIONER...
Page 176: ...7 6 R32 2 3 1 1 X 2 R32...
Page 177: ...7 7 ON OFF OFF...
Page 179: ...7 9 1 1 AAA 2 T T 1 M3 16L 2 2 1 1 1 1 1 2 3 7...
Page 180: ...7 10 3 2000...
Page 183: ...7 13 2 1 65 2 3 4 65 3 1 2 3 4 5 6...
Page 184: ...7 14 1 2 3 1 2 3 4 5 6 Mounting plate 7 8 M4 12L 1 50 M4 12L 2 4...
Page 185: ...7 15 50 50 55 4 16 16 16 16 16 16...
Page 192: ...7 22 R32 13 25 OFN...
Page 193: ...7 23 a b c d e f g h 80 i j k...
Page 194: ...7 24 1 2...
Page 195: ...7 25 ON OFF 1 OFF ON 2 1 LED INDICATOR LIGHTS ON OFF SWITCH MODE DISPLAY IR RECEIVER TIMER...
Page 197: ...7 27 10 CO2 GWP 1000 1 2 PCB 10 3...
Page 198: ...7 28...
Page 200: ...8 2 FTXC20 25 35 50 785 250 288 FTXC60 71 1005 288 297 mm mm...
Page 202: ...8 4 RXC71 930 695 66 12 610 241 350 23 350 75 98 mm...
Page 203: ...8 5 R32 DAIKIN AIR CONDITIONER...
Page 204: ...8 6 R32 2 3 1 m 1m Xm2 R32...
Page 205: ...8 7 OFF...
Page 207: ...8 9 1 1 AAA 2 T T 1 M3 16L 2 2 1 1 1 1 inverter 1 2 3 7...
Page 208: ...8 10 3 2000...
Page 211: ...8 13 2 1 65mm 2 3 4 A 65 3 1 2 3 4 5 6...
Page 212: ...8 14 1 2 3 1 2 3 4 5 6 7 8 M4 12L 1 4mm 50 mm VP 30 M4 12L 2...
Page 213: ...8 15 50 50 55 mm 4 16 16mm 16mm 16 16mm 16mm...
Page 220: ...8 22 t LFL R32 LFL 13 25 OFN OFN OFN OFN OFN...
Page 221: ...8 23 a b c d e f g h 80 i j k...
Page 222: ...8 24 1 2...
Page 225: ...8 27 10 CO2 GWP kg 1000 1 2 PCB 10 3...
Page 226: ...8 28...
Page 254: ...9 28 MEMO...
Page 282: ...10 28 MEMO...
Page 310: ...11 28 NOTATKI...
Page 317: ......
Page 318: ......
Page 319: ......