ESIE13-03
|
Part 2. Troubleshooting
2. Error code based troubleshooting
Page 22
13/05/15
|
Version 2.0
Ground source heat pump
2.5. “CJ-02” – User interface room temperature error
2.6. “C0” – Flow sensor error
2.7. “C4” – Refrigerant liquid thermistor R3T (A1P) abnormality
2.8. “EC” – Domestic hot water temperature error
Trigger
Effect
Reset
Room temperature thermistor of user
interface detects an abnormal value (open
or short circuit).
Unit will keep operating.
Auto-reset.
Possible cause
Check
Corrective action
Faulty room thermistor of user interface.
Check room thermistor read out value via
the user interface and compare with
actual room temperature.
Replace user interface or replace hydro
PCB A1P (see
Trigger
Effect
Reset
Flow sensor still detects a water flow after
45 seconds when pump has stopped.
Unit will stop operating.
Via user interface.
Possible cause
Check
Corrective action
Water flow caused by external pump.
Check if another (external) pump is
installed on the same water circuit.
Correct hydraulic field circuit. Refer to the
Installer Reference Guide.
Faulty flow sensor / hydro PCB A1P.
Check flow sensor (see
).
Replace flow sensor (see
replace hydro PCB A1P (see
If flow sensor failed due to contamination,
check for source of contamination and
consider to install an additional water fil-
ter.
Trigger
Effect
Reset
Thermistor detects an abnormal value
(open or short circuit).
Unit will stop operating.
Auto-reset when problem is solved.
Possible cause
Check
Corrective action
Faulty refrigerant liquid thermistor R3T
(A1P) / hydro PCB A1P.
Check thermistor R3T (see
Replace thermistor R3T (see
) or
hydro PCB (see
Trigger
Effect
Reset
R5T (A1P) (water tank thermistor) detects
temperature above 89°C.
Unit will continue operating.
Auto-reset when trouble is solved.
Possible cause
Check
Corrective action
Increased water temp by external heat
source.
Check if another heat source is installed
on the same water circuit.
Correct hydraulic field circuit. Refer to the
Installer Reference Guide.
Faulty water tank thermistor R5T / hydro
PCB A1P.
Check thermistor R5T (see
Replace thermistor R5T (see
) or
hydro PCB A1P (see
).