ESIE13-03
|
Part 2. Troubleshooting
4. Component checklist
Page 74
13/05/15
|
Version 2.0
Ground source heat pump
Visual check
1. If thermal protector backup heater Q1L has tripped, press the red button to reset thermal protector backup heater Q1L.
Functional check
1. If required, check the thermal protector backup heater Q1L trip temperature by submerging the sensor in water.
2. Heat the water and measure the temperature of the water. The thermal protector backup heater Q1L must trip at approximately
92°C.
1. Switch off the Daikin Altherma GSHP via the user interface.
2. Remove the switch box cover, refer to
"Removing the switch box cover" on page 89
3. Remove the 2 screws that fix the thermal protector backup heater Q1L.
4. Disconnect the wiring from the thermal protector backup heater Q1L.
5. Measure the resistance between Q1L terminals 31 - 32 and measure the resistance between Q1L terminals 11 - 12, both
contacts must be closed.
6. If one or more measurements fail, replace the thermal protector backup heater Q1L, refer to
"Replacing the thermal protector
.
Mechanical check
Electrical check