ESIE13-03
|
Part 3. Repair
2. Unit specific repair procedures
Page 106
13/05/15
|
Version 2.0
Ground source heat pump
Figure 24 - Replacing the brine pump
Installation
1. Proceed in reverse order.
2. Fill the brine circuit, refer to “To fill the brine circuit” in the Daikin Altherma ground source heat pump Installer reference guide.
2.2.8. Replacing the backup heater
2.2.8.1 Preliminary actions
1. Switch off the Daikin Altherma GSHP via the user interface.
2. Remove the front panel, refer to
"Removing the front panel" on page 85
.
3. Remove the switch box cover, refer to
"Removing the switch box cover" on page 89
4. Unlock the power input section, refer to
"Unlocking the pivoting power input section" on page 90
5. Drain the water circuit, refer to
"Draining the water circuit" on page 87
1. Screw
6. Brine pump wire
2. A9 PCB
7. Nut
3. Brine pump ground wire
8. Brine pump
4. K6M contacts 3-4
9. Seal
5. X77A
C
AUTION
Make sure to connect the brine pump ground wire and the A9P PCB ground wire to the chassis. If damaged, replace
the seals.
5
2
6
7
9
8
7
6
3
1
4