ESIE13-03
|
Part 3. Repair
2. Unit specific repair procedures
Page 140
13/05/15
|
Version 2.0
Ground source heat pump
10. Remove the refrigerant high pressure sensor (2).
Figure 60 - Replacing the refrigerant high pressure sensor - 3
Installation
1. Proceed in reverse order.
2.2.23. Replacing the refrigerant high pressure switch
2.2.23.1 Preliminary actions
1. Remove the front panel, refer to
"Removing the front panel" on page 85
.
2. Remove the switch box cover, refer to
"Removing the switch box cover" on page 89
3. Open the Sound Insulation of the heat pump module (front side only),
"Opening the sound insulation of the heat pump module
.
2.2.23.2 Procedure
Removal
1. Unplug connector X32A (1) from the A10P PCB (2).
2. Attach a pull line (4) of approximately 2 meter to the refrigerant high pressure switch wire (3).
3. Cut the tie wraps (5).
4. While guiding the pull line (4) pull the refrigerant high pressure switch wire (3) until the pull line (4) surfaces at the heat pump
module.
1. Welding blanket (not illustrated)
3. Cooling clamp (not illustrated)
2. Refrigerant high pressure sensor
C
AUTION
Use welding blankets to protect the components that surround the refrigerant high pressure sensor.
Use 2 cooling clamps to protect the refrigerant high pressure sensor during brazing.
I
NFORMATION
The refrigerant high pressure switch wire is replaced with the refrigerant high pressure switch. A pull line must be
attached to the refrigerant high pressure sensor switch before removing the wire.
2