ESIE13-03
|
Part 2. Troubleshooting
4. Component checklist
13/05/15
|
Version 2.0
Page 77
Ground source heat pump
4.16. Water flow sensor B1L
1. Check that the arrow on flow sensor B1L matches the flow direction (arrow must point to the left).
1. Switch off the Daikin Altherma GSHP via the user interface.
2. Remove the switch box cover, refer to
"Removing the switch box cover" on page 89
.
3. Power the Daikin Altherma GSHP.
4. Activate “Installer level” on the user interface, refer to “Installer Level Settings” on the user interface are available in the
Installer Reference Guide, paragraph To access the most used commands.
5. On the user interface, select Actuator test run A.7.4.
6. On the user interface, activate the water pump (A.7.4.6).
7. On the user interface, select Flow Rate 6.1.8.
8. The displayed flow rate must be between 10 and 40 l/minute.
Technical specification
Description
The water flow sensor output signal versus flow is shown in the graph below.
The water flow sensor measures the flow in the
water circuit.
Location
Piping diagram
Switch box
Unit
Check procedure
Mechanical check
Electrical check
I
NFORMATION
The flow sensor B1L connector must be plugged into X4A on PCB A01P.