ESIE13-03
|
Part 1. Introduction
3. General operation of ground source heat pump
Page 14
13/05/15
|
Version 2.0
Ground source heat pump
When space heating thermo on is decided:
•
The brine pump will start operating with a continuous speed.
•
The inverter water pump will gradually adjust its speed to reach and maintain the required delta T (this is the water temperature
difference between the leaving water and entering water (refer to field setting [9-09] in
)).
•
The inverter compressor (after pressure equalisation) will gradually adjust its speed to reach and maintain the required water
temperature.
When the domestic hot water function is activated, the 3-way valve will switch over to the domestic hot water tank and space
heating side is closed. Domestic hot water and space heating cannot be active simultaneously. The 3-way valve will switch back
to space heating when domestic hot water setpoint is reached or when running timers are finished (refer to the Installer Reference
Guide for more details).
When the unit receives a thermo off signal:
•
The compressor will stop its operation.
•
The brine pump will operate for another 45 seconds (pressure equalization) and eventually stop.
•
The water pump will operate for some minutes and eventually stop or start sampling.