ESIE13-03
|
Part 3. Repair
2. Unit specific repair procedures
Page 144
13/05/15
|
Version 2.0
Ground source heat pump
Removal
The procedure below showing R2T in can be used for all thermistors except R10T.
1. Cut the tie wraps (1) that fix the insulation (3) and the sensor wire (2).
2. Slide the insulation (3) aside.
Figure 66 - Replacing a temperature sensor - 1
1. Press the clip (1) that fixes the sensor (2).
2. Remove the sensor (2) from the sensor holder (3).
Thermistor
Processed on PCB
Connector: pin
Access Information
R1T in (outlet water)
A1P
X5A: 1-2
Access via front of heat pump module, displace water
expansion vessel, refer to
"Replacing the water expansion
R2T in (after BUH)
A1P
X6A: 1-2
Access via front of heat pump module.
R3T in (refrigerant liquid)
A1P
X7A: 1-2
Access via front of heat pump module, displace water
expansion vessel, refer to
"Replacing the water expansion
R4T in (inlet water)
A1P
X8A: 5-6
R5T in (domestic hot
water tank)
A1P
X9A: 1-2
Turn the pivoting power input section, open domestic hot
water tank insulation.
R1T out (ambient air)
A9P
X5M: 11-12
Outdoor sensor.
R2T out (discharge)
A9P
X12A: 1-2
These 4 thermistors must be replaced together.
Access via front of heat pump module for R3T, R4T and
R5T; displace water expansion vessel, refer to
the water expansion vessel" on page 123
.
Access via rear of heat pump module for R2T; displace
brine expansion vessel, refer to
and open rear of heat
pump module.
R3T out (suction)
A9P
X12A: 3-4
R4T out (2 phase Tx)
A9P
X12A: 5-6
R5T out (brine entering)
A9P
X12A: 7-8
R6T out (brine leaving)
A9P
X13A: 1-2
Access via front of heat pump module, displace water
expansion vessel, refer to
"Opening the sound insulation of
the heat pump module (front side only)" on page 89
1. Tie wrap
4. Sensor holder
2. Sensor wire
5. Clip
3. Insulation
1
2
3
5
4
2