ESIE13-03
|
Part 3. Repair
2. Unit specific repair procedures
Page 86
13/05/15
|
Version 2.0
Ground source heat pump
2.1.2. Refrigerant Handling
2.1.2.1 Procedure
1. Switch off the Daikin Altherma GSHP via the user interface.
2. Remove the front panel,
"Removing the front panel" on page 85
3. Open the sound insulation of the heat pump module (front side), refer to
"Opening the sound insulation of the heat pump
module (front side only)" on page 89
.
Figure 5 - Refrigerant service ports
2.1.3. Draining the brine circuit
2.1.3.1 Procedure
1. Switch off the Daikin Altherma GSHP via the user interface.
2. Open the sound insulation of the heat pump module (front side), refer to
"Opening the sound insulation of the heat pump
module (front side only)" on page 89
.
3. Connect a hose to the brine circuit drain (1).
Refrigerant Action
High Pressure Service Port
Low Pressure Service Port
Recover
x
x
Vacuum
x
x
Charge
x
-
1. Low pressure service port
2. High pressure service port
W
ARNING
All hazardous waste shall be managed in accordance with federal, state and local regulations.
2
1