ESIE13-03
|
Part 3. Repair
2. Unit specific repair procedures
Page 108
13/05/15
|
Version 2.0
Ground source heat pump
7. Remove the thermal protector backup heater (1) from the backup heater (6).
8. Remove the backup heater wiring from behind X1M (2).
9. Unplug the connectors X1H and X2H (3).
10. Guide the wire with connector X2H (3) through the pivoting power input section bottom grommet (8).
11. Guide the wire with connector X1H (3) through the pivoting power input section side grommet (9).
12. Loosen the nut (4) that fixes the domestic hot water pump (5) to the backup heater (6).
13. Remove the seal (7).
Figure 26 - Replacing the backup heater - 2
Installation
1. Proceed in reverse order.
2. Fill the water circuit, refer to “To fill the space heating circuit” in the Daikin Altherma ground source heat pump Installer
reference guide.
3. Purge the water circuit, refer to “9.3 Air purge function on the space heating circuit” in the Daikin Altherma ground source heat
pump Installer reference guide.
1. Thermal protector backup heater Q1L
6. Backup heater
2. X1M
7. Seal
3. X1H, X2H
8. Bottom grommet
4. Nut
9. Side grommet
5. Water pump
I
NFORMATION
After installation, the backup heater positioning must allow to remove the thermal protector backup heater without
removing the backup heater. If damaged, replace the seals.
3
2
8
9
6
1
5
4
7