ESIE13-03
|
Part 3. Repair
2. Unit specific repair procedures
13/05/15
|
Version 2.0
Page 109
Ground source heat pump
2.2.9. Replacing the thermal protector backup heater
2.2.9.1 Preliminary actions
1. Switch off the Daikin Altherma GSHP via the user interface.
2. Remove the front panel, refer to
"Removing the front panel" on page 85
3. Remove the switch box cover, refer to
"Removing the switch box cover" on page 89
.
2.2.9.2 Procedure
Removal
1. Cut the tie wrap (1) that fixes the thermal protector backup heater capillary (2) to the chassis.
2. Pull the thermal protector backup heater (3) out of the backup heater (7).
3. Loosen and remove the 2 screws (4) that fix the thermal protector backup heater bracket (5).
4. Loosen and remove the 2 screws (6) that fix the thermal protector backup heater (3).
5. Remove the wiring from the wire terminals (8) of the thermal protector backup heater (3).
6. Remove the thermal protector backup heater (3) while guiding the capillary (2) through the grommet (9) at the bottom of the
pivoting power input section.
Figure 27 - Replacing the thermal protector backup heater
1. Tie wrap
6. Screw
2. Thermal protector backup heater capillary
7. Backup heater
3. Thermal protector backup heater
8. Wire terminal
4. Screw
9. Grommet
5. Thermal protector backup heater bracket
1
9
2
2
2
3
4
3
8
6
4
7
8
5