Part 2. Troubleshooting
4. Component checklist
13/05/15
|
Version 2.0
Page 79
Ground source heat pump
4.17. 3-way valve M3S
1. Switch off the Daikin Altherma GSHP via the user interface.
2. Remove the top panel, refer to
"Removing the top panel" on page 88
.
3. Check that the knob is fully pressed (= motor control).
4. Check that the knob is either in domestic hot water or space heating position but not in an intermediate position.
1. Switch off the Daikin Altherma GSHP via the user interface.
2. Remove the top panel, refer to
"Removing the top panel" on page 88
.
3. Remove the switch box cover, refer to
"Removing the switch box cover" on page 89
.
4. Power the Daikin Altherma GSHP and activate domestic hot water.
Technical specification
Description
The 3-way valve is driven by a 230 VAC motor. Motor and valve can be replaced
separately.
The 3-way valve is used to circulate the water in
the water circuit through the domestic hot water
tank or through the space heating circuit.
Location
Piping diagram
Switch box
Unit
Check procedure
Mechanical check
Electrical check