ESIE13-03
|
Part 3. Repair
2. Unit specific repair procedures
13/05/15
|
Version 2.0
Page 125
Ground source heat pump
Installation
1. Proceed in reverse order.
2. Fill the brine circuit, refer to “To fill the brine circuit” in the Daikin Altherma ground source heat pump Installer reference guide.
2.2.16. Replacing the 3-way valve motor
2.2.16.1 Preliminary actions
1. Switch off the Daikin Altherma GSHP via the user interface.
2. Remove the front panel, refer to
"Removing the front panel" on page 85
3. Remove the top panel, refer to
"Removing the top panel" on page 88
.
4. Remove the switch box cover, refer to
"Removing the switch box cover" on page 89
.
2.2.16.2 Procedure
Removal
1. Unplug connectors X33A
and X85A
from the A1P PCB
(3)
.
2. Loosen and remove the 2 screws
(4)
that fix the fixation plate
.
3. Detach the right side of the fixation plate
.
4. Flip the fixation plate
.
C
AUTION
If damaged, replace the seal (6).
C
AUTION
If required, adjust the pressure of the brine expansion vessel (4).
I
NFORMATION
The 3-way valve wire is replaced together with the 3-way valve motor. To facilitate the installation of new 3-way valve
motor, a pull line must be attached to the 3-way valve motor wire before removal.