ESIE13-03
|
Part 3. Repair
2. Unit specific repair procedures
Page 100
13/05/15
|
Version 2.0
Ground source heat pump
Figure 19 - Brine filter installation
1. Proceed in reverse order.
2. Fill the brine circuit, refer to “To fill the brine circuit” in the Daikin Altherma ground source heat pump Installer reference guide.
3. Check the brine concentration.
2.2.4. Cleaning the water filter
2.2.4.1 Preliminary actions
1. Switch off the Daikin Altherma GSHP via the user interface.
2. Remove the front panel, refer to
"Removing the front panel" on page 85
.
3. Remove the top panel, refer to
"Removing the top panel" on page 88
4. Partially drain the water circuit, refer to
"Draining the water circuit" on page 87
.
2.2.4.2 Procedure
Removal
1. Place a cloth (1) under the water filter (3).
2. Remove the clip (2) that fixes the water filter (3).
3. Pull the water filter (3) to remove it from the filter housing.
4. Clean the water filter (3) with water and a soft brush.
C
AUTION
Although the water circuit is partially drained, some water may be spilled when removing the water filter. Always wipe
off spilled water.