ESIE13-03
|
Part 3. Repair
2. Unit specific repair procedures
Page 124
13/05/15
|
Version 2.0
Ground source heat pump
1. Proceed in reverse order.
2. Fill the water circuit, refer to “To fill the space heating circuit” in the Daikin Altherma ground source heat pump Installer
reference guide.
3. Purge the water circuit, refer to “9.3 Air purge function on the space heating circuit” in the Daikin Altherma ground source heat
pump Installer reference guide.
2.2.15. Replacing the brine expansion vessel
2.2.15.1 Preliminary actions
1. Switch off the Daikin Altherma GSHP via the user interface.
2. Remove the lower rear panel, refer to
"Removing the lower rear panel" on page 92
2.2.15.2 Procedure
Removal
1. Loosen but do not remove the 2 screws (
) that fix the upper brine expansion vessel support (
).
2. Remove the brine expansion vessel (
) from the lower brine expansion vessel support (
) and put it aside.
3. Loosen the nut (
) that fixes the flexible hose.
4. Remove the brine expansion vessel (
).
5. Remove the seal
Figure 43 - Replacing the brine expansion vessel
1. Screw
4. Brine expansion vessel
2. Upper brine expansion vessel support
5. Nut
3. Lower brine expansion vessel support
6. Seal
3
4
3
3
2
1
2
5
6