ESIE13-03
|
Part 5. Appendix
1. Field settings
13/05/15
|
Version 2.0
Page 159
Ground source heat pump
Figure 75 - Field settings table 2-3
Breadcrumb
Field code
Range, step
Default valu e
Date
Value
Field settings table
Installer setting at variance with
default value
Setting name
A.8
[8-08]
20
A.8
[8-09]
R/W
[9-01]~[9-00], step: 1°C
55°C
A.8
[8-0A]
R/W
[9-01]~[9-00], step: 1°C
45°C
A.8
[8-0B]
13
A.8
[8-0C]
10
A.8
[8-0D]
16
A.8
[9-00]
R/W
37~65°C, step: 1°C
65°C
A.8
[9-01]
R/W
15~37°C, step: 1°C
24°C
A.8
[9-02]
22
A.8
[9-03]
5
A.8
[9-04]
R/W
1~4°C, step: 1°C
1°C
A.8
[9-05]
R/W
15~37°C, step: 1°C
24°C
A.8
[9-06]
R/W
37~65°C, step: 1°C
65°C
A.8
[9-07]
5
A.8
[9-08]
22
A.8
[9-09]
R/W
3~10°C, step: 1°C
8°C
A.8
[9-0A]
5
A.8
[9-0B]
R/W
0: Quick
1: Slow
A.8
[9-0C]
R/W
1~6°C, step: 0,5°C
1 °C
A.8
[9-0D]
R/W
0~8,step:1
6
A.8
[9-0E]
0~8,step:1
6
A.8
[A-00]
1
A.8
[A-01]
0
A.8
[A-02]
0
A.8
[A-03]
R/W
0: 148Hz
1: 193Hz
A.8
[A-04]
R/W
0: 0°C
1: -2°C
2: -4°C
3: -6°C
4: -8°C
5: -10°C
6: -12°C
7: -14°C
A.8
[B-00]
0
A.8
[B-01]
0
A.8
[B-02]
0
A.8
[B-03]
0
A.8
[B-04]
0
A.8
[C-00]
1
A.8
[C-01]
0
A.8
[C-02]
R/W
0: No
1: Bivalent
2: -
3: -
A.8
[C-03]
R/W
-25~25°C, step: 1°C
0°C
A.8
[C-04]
R/W
2~10°C, step: 1°C
3°C
A.8
[C-05]
R/W
1: Thermo ON/OFF
2: C/H re quest
A.8
[C-06]
R/W
0: -
1: Thermo ON/OFF
2: C/H re quest
A.8
[C-07]
R/W
0: LWT control
1: Ext RT control
2: RT control
A.8
[C-08]
R/W
0: No
1: Outdoor sensor (##)
2: Room sensor
A.8
[C-09]
R/W
0: Normally open
1: Normall y closed
A.8
[C-0A]
0
A.8
[C-0C]
0
A.8
[C-0D]
0
A.8
[C-0E]
0
A.8
[D-00]
R/O
0: Non e
A.8
[D-01]
R/W
0: No
1: Active open
2: Active closed
A.8
[D-02]
R/W
0: No
1: Secondary rtrn
2: Disinf. Shunt
A.8
[D-03]
R/W
0: Disabled
1: Enabled, shift 2°C (from -2 to 2°C)
2: Enabled, shift 4°C (from -2 to 2°C)
3: Enabled, shift 2°C (from -4 to 4°C)
4: Enabled, shift 4°C
(from -4 to 4°C )
A.8
[D-04]
R/W
0: No
1: Pwr consm p ctrl
A.8
[D-05]
R/W
0: Forced off
1: As normal
A.8
[D-07]
R/O
0: No (#)
A.8
[D-08]
R/W
0 (No): NOT installed
1: Installed (0.1 pulse/kWh)
2: Installed (1 pulse/kWh)
3: Installed (10 pulse/kWh)
4: Installed (100 pulse/kWh)
5: Installed (1000 pulse/kWh )
Is a solar kit connected?
Is an external kWh meter used for power measurement?
Which heaters are permitted if prefer. kWh rate PS is cut?
Contact type of preferential kWh rate PS installation?
Which type of DHW pump is installed?
Leaving water temperature compensation around 0°C.
Is a demand PCB connected?
Is the pump allowed to run if prefer. kWh rate PS is cut?
--
--
--
--
Bivalent hysteresis temperature.
What is the thermo request contact type for the main zone?
What is the thermo request contact type for the add. zone?
What is the unit control method in space operation?
Which type of external sensor is installed?
What is the required alarm output contact type?
--
--
--
--
Is an external backup heat source connected?
Bivalent activation temperature.
--
Maximum heating frequency
What is the brine anti freeze up temperature?
--
--
--
What is the desired delta T in heating?
--
What emitter type is connected to the main LWT zone?
Room temperature hysteresis.
--
--
--
Leaving water temperature overshoot temperature.
What is the mimimum desired LWT for add. zone in heating?
What is the maximum desired LWT for add. zone in heating?
--
--
--
--
--
What is the maximum desired LWT for main zone in heating?
What is the mimimum desired LWT for main zone in heating?
--
--
What is the desired comfort main LWT in heating?
What is the desired eco main LWT in heating?
Pump speed limitation
--
(*) This setting is not applicable for this unit. Do not change the default value.
*GSQH10S18AA9W
4P359382-1D - 2015.02
Breadcrumb
Field code
Range, step
Default valu e
Date
Value
Field settings table
Installer setting at variance with
default value
Setting name
A.8
[D-09]
R/W
0 (No): NOT installed
1: Installed (0.1 pulse/kWh)
2: Installed (1 pulse/kWh)
3: Installed (10 pulse/kWh)
4: Installed (100 pulse/kWh)
5: Installed (1000 pulse/kWh )
A.8
[D-0A]
0
A.8
[D-0B]
2
A.8
[D-0C]
0
A.8
[D-0D]
0
A.8
[D-0E]
0
A.8
[E-00]
R/O
0~5
5: Ground sourc
e
A.8
[E-01]
R/O
1: 16
A.8
[E-02]
R/O
1: T yp e 2
A.8
[E-03]
2
A.8
[E-04]
R/O
0: No
A.8
[E-05]
1
A.8
[E-06]
1
A.8
[E-07]
1
A.8
[E-08]
0
A.8
[E-09]
0
A.8
[E-0A]
0
A.8
[E-0B]
R/O
0 (#)
A.8
[E-0C]
0
A.8
[F-00]
R/W
0: Disabled
1: Enabled
A.8
[F-01]
20
A.8
[F-02]
3
A.8
[F-03]
5
A.8
[F-04]
0
A.8
[F-05]
0
A.8
[F-06]
0
A.8
[F-09]
R/W
0: Disabled
1: Enabled
A.8
[F-0A]
0
A.8
[F-0B]
R/W
0: No
1: Yes
A.8
[F-0C]
1
A.8
[F-0D]
R/W
0: Continuous
1: Sample
(only possible if [C-07] = 0)
2: Re quest (only possible if [C-07 ] ≠ 0 )
--
What is the pump operation mode?
--
--
--
--
Pump operation during flow abnormality.
--
Close shut-off valve during thermo OFF?
--
Is the power saving function available on the outdoor unit?
--
--
--
Which type of compressor is installed?
What is the indoor unit software type?
--
Pump operation allowed outside range.
--
--
Is an external kWh meter used for power measurement?
--
--
--
--
Which type of unit is installed?
--
--
Is a bi-zone kit installed ?
--
--
(*) This setting is not applicable for this unit. Do not change the default value.