ESIE13-03
|
Part 3. Repair
2. Unit specific repair procedures
13/05/15
|
Version 2.0
Page 93
Ground source heat pump
Figure 12 - Removing the lower rear panel
Installation
1. Proceed in reverse order.
2.2.2. Replacing a PCB in the switch box
2.2.2.1 Preliminary actions
1. Switch off the Daikin Altherma GSHP with the field supplied circuit breaker.
2. Remove the front panel, refer to
"Removing the front panel" on page 85
3. Remove the switch box cover, refer to
"Removing the switch box cover" on page 89
.
2.2.2.2 Procedure: replacing the A1P PCB
Removal
1. Unplug connectors X33A (1) and X85A (2) from the A1P PCB (5).
2. Loosen and remove the 2 screws (3) that fix the fixation plate (4).
3. Detach the right side of the fixation plate (4).
4. Flip the fixation plate (4).
5. Unplug all connectors from the A1P PCB.
6. Carefully pull the A1P PCB (5) at the right side and unlatch the 11 pcb supports (6) one by one using a small pliers.
7. Remove the A1P PCB (5).
1. Screw
3. Brine drain hose
2. Lower rear panel
4. Domestic hot water drain hose
W
ARNING
Electrical shock hazard. Remove power from the Daikin Altherma GSHP before removing the switch box cover.
Do not touch terminals.
1
2
1
1
1
1
1
1
4
3
1