Proprietary Information: Not for use or disclosure except by written agreement with Clearfield.
86
FieldSmart
®
Fiber Active Cabinet (FAC) 3200
Installation Manual
_________________________________________________________
Step 1:
Step 2:
Step 3:
Step 4:
Step 5:
Step 6:
Step 7:
Step 8:
To install batteries
At the rectifier shelf, open the fuse panel door. Verify that the battery breakers are
OFF
.
Remove the battery compartment door. See
Operating Cabinet Doors
for instructions.
In the battery compartment, disconnect the #10 AWG
battery power cables from the power supply leads and
set the cables aside.
Place a string of four batteries into the battery compartment, with the terminals in front.
Install the jumper straps between the battery terminal posts per the manufacturer instructions.
Connect the battery power cables as follows:
a.
Remove the protective caps from the cable ring lugs.
b.
Attach the black cable to the positive (+) terminal post
at the right end of the string.
c.
Attach the red cable to the negative (-) terminal post at
the left end of the string.
ALERT!
Check all connections carefully to verify correct
wiring polarities.
d.
Install the temperature compensation cable lug onto
the string’s negative (-) terminal post.
e.
Tighten the hardware on the terminal posts to the torque specified by the manufacturer.
Reconnect the battery power cables to the power supply leads.
Note:
If you are using the optional seismic protection kit, install the front bracket around the installed batteries.
See Installing a Seismic Protection Kit for instructions.
Replace the battery compartment door.