Installing AC Power (220-240 VAC)
Note:
The cabinet ships from the factory equipped to support 220-240 VAC service. However, the cabinet AC load center
can be reconfigured to support 110-120 VAC service if required. See Installing AC Power (110-120 VAC) for details.
Install 220-240 VAC power as described below.
DANGER!
High voltage may be present. Do not apply AC power to the cabinet until the installation process is
complete.
WARNING!
Electrical hazard. Only a qualified electrician should perform this procedure.
Before proceeding, verify that AC service to the cabinet site is OFF at the local power transfer switch.
To install the cabinet ground connection
Open the splice compartment door.
At the cabinet AC load center, switch all breakers to the OFF position.
Remove the left cover panel from the AC load center.
Remove the AC duct cover (two panels) as follows:
a.
Loosen (but do not remove) the mounting screws securing the duct cover panels to the fixture.
b.
Slide the upper panel sideways to align its two keyholes with the two mounting screws. When aligned, pull
the panel away from the fixture.
c.
Slide the lower panel sideways to align its two keyholes with the two mounting screws. When aligned, pull
the panel away from the fixture.
Pull the AC cable into the cabinet through the entry hole in the base of the compartment.
Route the AC cable up through the duct and feed it into a hole on the left side of the AC load center.
Remove the Main Service Disconnect breaker from the load center housing to ease wire termination. Pull the
breaker straight out to disengage it from the assembly.