129
FieldSmart
®
Fiber Active Cabinet (FAC) 3200
__________________________________________________________
Installation Manual
Direct: 763.476.6866 • National: 800.422.2537 • www.SeeClearfield.com • [email protected]
Manual 020421 REV A - Jan 2019
Step 1:
Step 2:
Step 3:
Step 4:
Step 5:
Programming the Valere Shelf Controller
The Valere shelf controller is factory programmed with appropriate settings for FAC cabinets. You can change the factory
defaults for the battery profile, temperature compensation, float voltage, and other settings. This section provides basic in
-
structions for accessing and programming the Valere shelf controller. For additional information on programming the Valere
shelf controller, see the Valere controller manual.
System configuration access
You can check the system status or modify settings from the controller display panel and three button keypad. Use the UP
and DOWN buttons to scroll through the functions. Use the MENU button to select and/or enter a sub-menu.
The controller provides three menu levels: Basic, Advanced, and Administrator. When the display reads
System OK
, the
controller is at the Basic menu level. Use the UP/DOWN buttons to sequentially view basic parameters. Press and hold the
MENU button for 5 seconds to access the Advanced menu level. Scroll to and select
Log In
to access the Administrator
level. The default username is
Admin
(case sensitive) and the default password is
5001
. The Administrator level allows you
to modify all the plant settings. To enter the password, use the MENU button to select the number (the character to be select
flashes) in the password, and use the UP/DOWN buttons to toggle to the next character. Toggle to the right-most arrow key
and press MENU to enter. The instructions below provide more detail.
To access the Administrator menu
With controller display showing
System OK
, press and hold
MENU
button for 5 seconds.
Scroll to
CHOOSE: >LOGIN
and press
MENU
. The display shows
PASSWORD ->0000<-
with the first 0 flash
-
ing.
Press
MENU
to change first digit value. Each press of the
MENU
button advances the value by one. Pressing
UP
selects that value for the first digit, which stops flashing, and advances to the second digit, which begins
flashing.
Repeat procedure above for all four digits. Press
UP
to select <, which will then flash, and press
MENU
.
Controller displays
OK: ADMIN
for 5 seconds.