Connect the AC wiring as follows:
• Connect the green (ground) lead to the ground bus bar.
• Connect the white (neutral) lead to the neutral bar.
• Connect the black L1 lead to the left side of the Main Service Disconnect breaker.
• Connect the red L2 lead to the right side of the Main Service Disconnect breaker.
Re-attach the Main Service Disconnect breaker into the load center.
Dress and secure the AC cable, providing adequate strain relief.
Replace the AC duct cover (two panels) and the left cover panel on the AC load center.
Step 8:
Step 9:
Step 10:
Step 11:
Installing AC Power (110-120 VAC)
The cabinet ships from the factory equipped to support 220-240 VAC service, but can be reconfigured to support 110-120
VAC service if required. Converting the AC load center to support 110-120 VAC input requires modification to existing wiring.
The 110-120 VAC input power option is only supported in conjunction with use of 20 Amp rectifier modules.
Note:
When supplied by 110-120 VAC input power, the cabinet supports a maximum load of 2160 Watts. If your application
requires a load that exceeds 2160 Watts, use a 220-240 VAC input power supply instead.
DANGER!
High voltage may be present. Do not apply AC power to the cabinet until the installation process is
complete.
WARNING!
Electrical hazard. Only a qualified electrician should perform this procedure.
Before proceeding, verify that AC service to the cabinet site is OFF at the local power transfer switch