90
SMARTFLOW II
How to Enter Calibration Mode
Two methods can be used to enter the Calibrate mode.
1. Only allows user to view the Cal factors. To enter
“View” Calibration Mode:
• Toggle the Spray Switch to
OFF.
• Press and hold the CAL button for 1 second.
The word “
CAL
” will be displayed in the
Application Rate display window and the
Data display window will show the Cal factors.
The red Warn
LED
will remain off as a reminder
the user cannot change the Cal factors.
To exit “View” Calibration Mode:
• Press
CAL
button for 1 second.
NOTE:
The audible alarm remains off
while in either Cal mode except when
fine tuning Flow Cal (where auto
control operates)
.
SPRAY
VAR
CONT
OFF
1 SEC
CAL
CAL
CALIBRATION