WWN card fault indicators
Before replacing a WWN card, verify that the replacement is necessary. Any of the following events can indicate that cards require
replacement:
•
RASlog messages may occur during periodic WWN card audit routines alerting you of data or license mismatches between
WWN cards and other errors. Some of these messages may direct you to contact technical support or to run the
wwnrecover
command. You can use this command to further verify or to fix problems. If an EM-1220 or EM-1222 error message occurs
due to WWN card data corruption or data mis-matches across WWN cards, data recovery may be possible using this
command. For more information on using
wwnrecover
, refer to
on page 171. If recovery is not
possible, command output will direct you to replace the affected card(s).
•
Status LEDs on the WWN bezel do not reflect the actual status of the WWN cards or indicate a problem. For information on
interpreting LED patterns, refer to
on page 109. Note that the LED patterns may temporarily
change during POST and other diagnostic tests.
•
Problems viewing or modifying the data stored on the WWN card.
•
Error messages regarding WWN units in
chassisshow
output.
Error messages that may indicate problems with a WWN card are summarized in the following table.
TABLE 25
Messages that may indicate WWN card failure
Type of message
Sample error message
WWN unit fails its field-replaceable unit
(FRU) header access.
0x24c (fabos): Switch: switchname, error
EM-I2C_TIMEOUT, 2, WWN 1 I2C
timed out: state 0x4
WWN unit fails to power on.
<timestamp>, [EM-1004],
<sequence-number>, CRITICAL,
<system-name>, WWN # failed to power
onor<timestamp>, [EM-1043],
<sequence-number>, WARNING,
<system-name>, Can't power <FRU Id>
<state (on or off)>.
WWN unit is being faulted.
0x24c (fabos): Switch: switchname
, Critical EM-WWN_UNKNOWN, 1, Unknown
WWN #2 is being faultedor<timestamp>,
[EM-1003], 40, SLOT 7 | FFDC | CHASSIS,
CRITICAL, Brocade_Chassis, WWN 2 has unknown
hardware identifier: FRU faultedor<timestamp>,
[EM-1034], <sequence-number>, ERROR,
<system-name>, WWN # set to faulty,
rc=<return code>
WWN unit is not present or is not accessible.
0x24c (fabos): Switch:
switchname, Error EM-WWN_ABSENT, 2,
WWN #1 not presentor<timestamp>,
[EM-1036], <sequence-number>, WARNING,
<system-name>, <FRU Id> is not
accessible.
Writing to the FRU history log
(
hilSetFruHistory
) has failed.
0x24c (fabos): Switch:
switchname, Error EM-HIL_FAIL, 2,
HIL Error: hilSetFruHistory failed,
rc=-3 for SLOT 3
WWN card fault indicators
Brocade X6-4 Director Hardware Installation Guide
53-1004106-07
169
Summary of Contents for X6-4
Page 12: ...Brocade X6 4 Director Hardware Installation Guide 12 53 1004106 07...
Page 20: ...Brocade X6 4 Director Hardware Installation Guide 20 53 1004106 07...
Page 28: ...Brocade X6 4 Director Hardware Installation Guide 28 53 1004106 07...
Page 64: ...Brocade X6 4 Director Hardware Installation Guide 64 53 1004106 07...
Page 86: ...Brocade X6 4 Director Hardware Installation Guide 86 53 1004106 07...
Page 102: ...Brocade X6 4 Director Hardware Installation Guide 102 53 1004106 07...
Page 130: ...Brocade X6 4 Director Hardware Installation Guide 130 53 1004106 07...
Page 140: ...Brocade X6 4 Director Hardware Installation Guide 140 53 1004106 07...
Page 166: ...Brocade X6 4 Director Hardware Installation Guide 166 53 1004106 07...
Page 196: ...Brocade X6 4 Director Hardware Installation Guide 196 53 1004106 07...
Page 200: ...Brocade X6 4 Director Hardware Installation Guide 200 53 1004106 07...
Page 204: ...Brocade X6 4 Director Hardware Installation Guide 204 53 1004106 07...
Page 210: ...Brocade X6 4 Director Hardware Installation Guide 210 53 1004106 07...
Page 224: ...Brocade X6 4 Director Hardware Installation Guide 224 53 1004106 07...
Page 238: ...Brocade X6 4 Director Hardware Installation Guide 238 53 1004106 07...