Chapter 6 P5 output terminal
85
The above function code is used to correct the zero drift of the analog output and the
deviation of the output amplitude. It can also be used to customize the required AO
output curve. If the zero offset is represented by "b", the gain is represented by k, the
actual output is represented by Y, and the standard output is represented by X, the
actual output is: Y = kX + b. Among them, the zero offset coefficient of AO1 and AO2
corresponds to 10V (or 20mA), and the standard output refers to the output of 0V~10V
(or 0mA~20mA) corresponding to the analog output without zero offset and gain
correction.
For example, if the analog output is the running frequency, it is desirable to output 8V
when the frequency is 0, and output 3V when the frequency is Maximum frequency, then
the gain should be set to “-0.50” and the zero offset should be set to “80%”.
P5-17
Y2 output delay time
0.0s
~
3600.0s
Default
:
0.0s
P5-18
Relay output delay
time
0.0s
~
3600.0s
Default
:
0.0s
P5-19
Relay 2 delay time
0.0s
~
3600.0s
Default
:
0.0s
P5-20
Y1 output delay time
0.0s
~
3600.0s
Default
:
0.0s
P5-21
Y3 delay time
(extended)
0.0s
~
3600.0s
Default
:
0.0s
Set the delay time of the output terminal from the state change to the actual output
change
P5-22
Output terminal
valid state
selection
Unit’s digit:Y2 Ten’s digit: Relay Hundred’s digit:
Relay 2
Thousand’s digit: Y1 million: Y3
0: The output terminal is connected to COM and the
disconnection is invalid.
1: The output terminal is not connected to COM,
and the disconnection is valid.
Default
:
00000
Define the valid state selection for the multi-function output terminal.
0: Positive logic, the digital output terminal and the corresponding common terminal are
connected to the active state, and the disconnection is in the invalid state;
1: Inverse logic, the digital output terminal and the corresponding common terminal are
connected to an inactive state, and the disconnection is in an active state.
P6 Group Start and stop control
P6-00
Start model
0: Direct start 1: Speed tracking restart
2: Pre-excitation start (AC asynchronous
machine)
Default
:
0
0
:
Direct start If the DC braking time is 0, the inverter will start running at the start
frequency. If the DC braking time is not 0, the DC braking is performed first, and then