Chapter 7 Faults and Solutions
133
acceleration
8, the frequency converter
selection is too small
power level
Deceleration
over current
Err03
1. There is grounding or short
circuit in the output circuit of the
inverter.
2. The control mode is vector
and there is no parameter
identification.
3, the deceleration time is too
short
4, the voltage is low
5, sudden load during
deceleration
6, no brake unit and brake
resistor installed
1, eliminate peripheral faults
2. Perform motor parameter
identification
3, increase the deceleration time
4, adjust the voltage to the normal
range
5, cancel the sudden load
6, install the brake unit and
resistor
Constant
speed
overcurrent
Err04
1. There is grounding or short
circuit in the output circuit of the
inverter.
2. The control mode is vector
and there is no parameter
identification.
3, the voltage is low
4. Is there a sudden load during
operation?
5, the frequency converter
selection is too small
1, eliminate peripheral faults
2. Perform motor parameter
identification
3. Adjust the voltage to the
normal range
4, cancel the sudden load
5, select the inverter with a larger
power level
Accelerated
overvoltage
Err05
1, the input voltage is too high
2. There is an external force
drag motor running during the
acceleration process.
3, the acceleration time is too
short
1. Adjust the voltage to the
normal range
2, cancel the additional power or
install braking resistor
3, increase the acceleration time
4, install the brake unit and