第四章、键盘操作
15
Chapter 4 Keypad operation
15
Digital display area
:
A total of 5 LED displays, which can display the set frequency, output frequency, various monitoring
data and alarm codes, etc.
Keyboard button description
button
name
function
PRG
Programming key
Enter or exit menu level I.
ENTER
Enter
Enter the menu interfaces level by level, and confirm
the parameter setting.
Increasing key
Increase data or function code.
Decreasing key
Decrease data or function code.
Menu move
selection /
monitoring key
Select the displayed parameters in turn in the stop or
running state, and select the digit to be modified when
modifying parameters.
RUN
Running key
Start the frequency inverter in the operation panel
control mode.
STOP/RE
S
Stop/Reset
Stop the operation when it is in the running state and
perform the reset operation when it is in the fault
state. The functions of this key are restricted by F7-
18.
JOG/REV
Multi-functional
Selection Key
Regulate the speed directly by panel potentiometer
when F0-10 is set to 10.
Table 4-1 Keypad function