Chapter 6 P0 group basic function
49
Chapter 6 Parameter Instruction
P0 Group Basic function group
P0-00
GP Type display
1:G type (constant torque load type)
2: P type (fan, pump type load type)
Default
:
1
This parameter is only for the user to view the factory model and cannot be
changed.
。
1: Constant torque load for specified rated parameters
2: Variable torque load (fan, pump load) for specified rated parameters
P0-01
Speed control mode
selection
0: No speed sensor vector control (SVC)
1: Speed sensor vector control (FVC)
2: V/F control
Default
:
0
0: No speed sensor vector control, open loop vector control, suitable for normal high
performance control applications, one inverter can only drive one motor. Such as
machine tools, centrifuges, wire drawing machines, injection molding machines and
other loads.
1: There is speed sensor vector control, closed loop vector control, the motor end must be
equipped with an encoder, the inverter must be equipped with the same type of PG
card as the encoder. Suitable for high precision speed control or torque control
applications. Only one motor can be driven by one inverter. Such as high-speed paper
machinery, lifting machinery, elevators and other loads.
2: V/F control, suitable for occasions where the load requirements are not high, or when
one inverter drives multiple motors, such as fans and pumps. It can be used in the case
where one inverter drives multiple motors.
Note:The motor parameter identification process must be performed when selecting
the vector control mode. Only accurate motor parameters can take advantage of
the vector control method to achieve better performance.
P0-02
Run
command
source selection
0: Operation panel command channel
(LED off)
1: terminal command channel (LED is lit)
2: Communication command channel
(LED flashing)
Default
:
0
Select the inverter running control command mode, the running command includes
start, stop, forward and reverse, jog, etc.
。
0: The operation panel command is controlled by the RUN, STOP and other buttons on the
operation panel.
1: Terminal command channel ("L/R" is on), which is controlled by the multi-function input
terminal.
2: Communication command channel ("L/R" flashing), the host computer controls the
running command through communication mode.