Chapter 9 Appendix
150
Stop/start parameter
Parameter
address
Parameter description
Parameter
address
Parameter description
1000
Communication set value(-
10000 ~ 10000)(Decimal)
1011
PID feedback
1001
Running frequency
1012
PLC process
1002
DC Bus voltage
1013
Pulse input frequency, unit:
0.01KHz
1003
Output voltage
1014
Feedback speed
1004
Output current
1015
Remaining running time
1005
Output power
1016
Voltage before AI1 correction
1006
Output torque
1017
Voltage before AI2 correction
1007
Running speed
1018
Voltage before AI3 correction
1008
DI input terminal
1019
Linear speed
1009
DO output terminal
101A
Present power-on time
100A
AI1 voltage
101B
Present running time
100B
AI2 voltage
101C
Pulse input frequency,
unit:1Hz
100C
AI3 voltage
101D
Communication setting value
100D
Counting value input
101E
Actual feedback speed
100E
Length value input
101F
Main frequency X display
100F
Load speed
1020
Auxiliary frequency Y display
1010
PID setting