122
Chapter 6 PC mutiple Multi-segment instruction,PLC
PC-41
The 11th paragraph
acceleration and
deceleration time
selection
0
~
3
Default
:
0
PC-42
Run time in paragraph
12
0.0s
(
h
)~
6553.5s
(
h
)
Default
:
0.0s(h)
PC-43
The 12th paragraph
acceleration and
deceleration time
selection
0
~
3
Default
:
0
PC-44
Run time of paragraph
13
0.0s
(
h
)~
6553.5s
(
h
)
Default
:
0.0s(h)
PC-45
The 13th paragraph
acceleration and
deceleration time
selection
0
~
3
Default
:
0
PC-46
Run time in paragraph
14
0.0s
(
h
)~
6553.5s
(
h
)
Default
:
0.0s(h)
PC-47
The 14th paragraph
acceleration and
deceleration time
selection
0
~
3
Default
:
0
PC-48
Run time in paragraph
15
0.0s
(
h
)~
6553.5s
(
h
)
Default
:
0.0s(h)
PC-49
The 15th paragraph
acceleration and
deceleration time
selection
0
~
3
Default
:
0
PC-50
Simple PLC runtime unit
0: s (seconds) 1: h (hours)
Default
:
0
PC-51
Multi-segment
instruction 0 given mode
0
:
Given by PC-00 1: given by AI1
2: AI2 given 3: panel potentiometer
4: PULSE pulse 5: PID given
6: P0-08 can be modified by UP/DOWN
Default
:
0
This parameter determines the given channel of the multi-segment instruction 0.
In addition to the PC-00, the multi-segment instruction 0 has a variety of other options to
facilitate switching between multiple short instructions and other given modes. When a
multi-segment command is used as a frequency source or a simple PLC as a frequency
source, switching between the two frequency sources can be easily realized.