Chapter 6 ,P9 Failure and protection
101
Output current limit
P8-36
Output current
ON
time
time
Output current overrun
detection signal
Output current overrun detection delay
time P8 -37
Figure 6-22 Schematic diagram of output current overrun detection
P8-38
Arbitrary arrival
current 1
0.0% to 300.0% (rated motor current)
Default
:
100.0%
P8-39
Arbitrary current 1
width
0.0% to 300.0% (rated motor current)
Default
:
0.0%
P8-40
Arbitrary arrival
current 2
0.0% to 300.0% (rated motor current)
Default
:
100.0%
P8-41
Arbitrary current 2
width
0.0% to 300.0% (rated motor current)
Default
:
0.0%
When the output current of the inverter is within the positive and negative detection width
of any set current, the inverter outputs an ON signal.
ON
Arbitrary arrival
current
Output current
ON
Time
ON
OFF
OFF
OFF
Arbitrary current width
Figure 6-23 Schematic diagram of arbitrary arrival current detection