Chapter 6 P5 output terminal
83
31
AI1 input overrun
When the value of analog input AI1 is greater than P8-46 (AI1
input protection upper limit) or less than P8-45 (AI1 input
protection lower limit), the ON signal is output.
32
Dropped
When the inverter is in the off state, it outputs an ON signal.
33
Reverse running
When the inverter is in reverse operation, it outputs ON signal.
34
Zero current state
Please refer to the description of function code P8-28, P8-29
35
Module temperature
reached
When the inverter module heatsink temperature (P7-07)
reaches the set module temperature arrival value (P8-47), the
ON signal is output.
36
Software current
overrun
Please refer to the description of function code P8-36, P8-37.
37
Lower limit
frequency arrival
(stop output also)
When the running frequency reaches the lower limit frequency,
the ON signal is output.
This signal is also ON during the stop state.
38
Alarm output
When the inverter fails and the fault handling mode is
continued, the ON signal is output.
39
Motor over
temperature alarm
When the motor temperature reaches P9-58, the output ON
signal
40
This running time
arrives
When the inverter runs for longer than P8-53, it outputs ON
signal.
P5-06
Y2 pulse output function
selection
Default: 0 running frequency
P5-07
AO output function selection
Default: 0 running frequency
P5-08
AO2 output function selection
(extension)
Default: 1 set frequency
The Y2 terminal output pulse frequency range is 0.01 kHz ~ P5-09 (between 0.01 and
100.00 kHz).
The analog output AO1 and AO2 output range is 0V ~ 10V, or 0mA ~ 20mA. The range
of pulse output or analog output, and the calibration relationship of the corresponding
function are shown in the following table
:
Set
value
Function
Function corresponding to pulse or analog output
0.0%~100.0%